Suitable for every boiler room
No fireclay used therefore quicker response times
Electronically monitored, therefore no wear
Equipment design by qualified HERZ technicians
 
 


 
 
 
 
 
 
 
 
 
 
Technical Specification
25
50
  90
  150
Output range kW            
9-30
15-50
27-90
45-150
Max. Permissible feed pressure mbar
0,10
0,10
0,10
0,15
Permissible operating pressure        bar 
3,0
3,0
3,0
3,0
Max. Permissible flow temperature    °C
90
90
90
90
Flue gas temperature   °C  
180
180
180
180
Flue gas mass flow       kg/s  
0,017
0,031
0,051
0,092
Water capacity L
133
133
215
350
Boiler weight       kg                  
730
735
1085
1390
Flow dimension (female thread) Zoll
6/4”
6/4”
6/4”
F 3”
Return flow dimension (female thread) Zoll
6/4”
6/4”
6/4”
F 3”
         

Equipment up to 1500kW on request

We reserve the rights for technical modifications
         
Dimensions (mm)
25
50
 90
150
A. Length
1415
1415
1555
2225
B. Width (maximum for access)  
850
850
920
1200
B1. Width (boiler)  
700
700
798
998
B2. Width overall 
2505
2505
2705
2905
C. Height  
1465
1465
1725
1725
D. Flue pipe diameter
160
180
180
250
E. Height - Inlet hopper door
320
320
320
320
F. Width - Inlet hopper door
500
500
600
800
G. Height for flue – centre line
976
976
1200
119
H. Height for flow/return connection
1310
1310
1505
1440
I. Height for return flow connection
-
-
-
770
J. Distance boiler – centre line to BSD
1255
1255
1305
1405
K. Distance for flow/return flow connection
516
516
595
--
L . Distance between the boiler to the end of the ash container
550
550
650
650
         
Copyright of EirTherm Ltd © 2006