Technical Specification |
25 |
50 |
90 |
150 |
| Output range kW |
9-30 |
15-50 |
27-90 |
45-150 |
| Max. Permissible feed pressure mbar |
0,10 |
0,10 |
0,10 |
0,15 |
| Permissible operating pressure bar |
3,0 |
3,0 |
3,0 |
3,0 |
| Max. Permissible flow temperature °C |
90 |
90 |
90 |
90 |
| Flue gas temperature °C |
180 |
180 |
180 |
180 |
| Flue gas mass flow kg/s |
0,017 |
0,031 |
0,051 |
0,092 |
| Water capacity L |
133 |
133 |
215 |
350 |
| Boiler weight kg |
730 |
735 |
1085 |
1390 |
| Flow dimension
(female thread) Zoll |
6/4” |
6/4” |
6/4” |
F 3” |
| Return flow dimension
(female thread) Zoll |
6/4” |
6/4” |
6/4” |
F 3” |
| |
|
|
|
|
Equipment up to 1500kW on request
|
We reserve the rights for technical modifications |
| |
|
|
|
|
| Dimensions (mm) |
25 |
50 |
90 |
150 |
| A. Length |
1415 |
1415 |
1555 |
2225 |
| B. Width (maximum for access) |
850 |
850 |
920 |
1200 |
| B1. Width (boiler) |
700 |
700 |
798 |
998 |
| B2. Width overall |
2505 |
2505 |
2705 |
2905 |
| C. Height |
1465 |
1465 |
1725 |
1725 |
| D. Flue pipe diameter |
160 |
180 |
180 |
250 |
| E. Height - Inlet hopper door |
320 |
320 |
320 |
320 |
| F. Width - Inlet hopper door |
500 |
500 |
600 |
800 |
| G. Height for flue – centre line |
976 |
976 |
1200 |
119 |
| H. Height for flow/return connection |
1310 |
1310 |
1505 |
1440 |
| I. Height for return flow connection |
- |
- |
- |
770 |
| J. Distance boiler – centre line to BSD |
1255 |
1255 |
1305 |
1405 |
| K. Distance for flow/return flow connection |
516 |
516 |
595 |
-- |
| L . Distance between the boiler to the
end of the ash container |
550 |
550 |
650 |
650 |
| |
|
|
|
|